Product Code: 111163604

Address:

Zhejiang,China

Main Products:

Miniature circuit breaker,moulded case circuit breaker,earth leakage circuit breaker,residual current circuit breaker,surge protective device

Contact Info.
C45N mini circuit breaker mcb
  • FOB Price
    Negotiable
  • Min. Order
    100 Piece(s)
  • Payment Terms
    -- --
  • Port
    Ningbo or Shanghai
  • Delivery Time
    0 days after payment
  • Place of Origin:
    Zhejiang China (Mainl...
  • Brand Name:
    hgg
  • Model Number:
    C45N
  • Type:
    Mini
  • Poles Number:
    1P,2P,3P,4P
  • Rated current:
    1~63A
  • Rated voltage:
    AC230/400V
  • Rated frequency:
    50/60HZ
  • No of poles:
    1P.2P.3P.4P
Product Description

DZ47-63(C45N) MINI CIRCUIT BREAKER

Products application:

DZ47-63(C45N) Series Miniature circuit breaker is used in lighting distribution system or motor distribution system for protection the overload or short circuit in the system. The product is neoteric in structure, light in weight, reliable and excellent in performance, it has high breaking capacity, can trip quickly, and its case and items are adopted by high fire-resistant and shockproof plastics. The product with long lift, is mainly used in AC 50/60HZ single pole 240V or two, three, four pole 415V circuit for overload and short-circuit protection as well as for unfrequented transformation and off switching electrical equipment and lighting circuit in normal condition. 

Products features:

·Breaking capacity highly, all rated current can be up to above 6KA.

·Double connection function, connect busbar and lead conveniently.

·With stored energy machine, contact close fast, avoid the disadvantage of manpower operated,Hence improve the using-life of products.

·with protection terminal, more safety.

·Many kinds of accessories can be choosed, in modularize and flexibility combine that make the customer install conveniently.

·The cover and function parts both are made of inflaming retarding,bear high temperature and bear impact plastic.

.The products comply with IEC60898/ GB10963 standard. 

Main technical specifications

Rated current(A)

Pole number

Rated working voltage(V)

Rated short circuit breaking capacity

Tripping curve

Test expected current(A)

6,10,16,20,25,32,40,50,

63

1,2

230/400

6000

 

B,C,D

 

1,2

230/400,240/415

6000

2,3,4

400/415

6000

Rated current: 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A

Rated frequency: 50/60HZ

Magnetic release operate: 

B curve: Between 3In and 5In

C curve: Between 5In and 10In

D curve: Between 10In and 14In

Mechanical life(O-C): No less than 20000 operations

Electrical life: No less than 6000 operations. 

Surge Current protect character:

Release rated current In

Started state

Test current

Specification time

Anticipate result

Remark

1~63

Cold state

1.31In

T≥1h

Not release

 

1~63

On top of above test

1.41In

T≥1h

Release 

Current rised steadily to specified value in 5s

In≤32

Cold state

2.55In

1s<t<60s

Release

 

In>32

Cold state

2.55In

1s<t<120s

Release

 

1~63

Cold state

3In

T≥0.1s

Not release

B type

1~63

Cold state

5In

T<0.1s

Release

B type

1~63

Cold state

5In

T≥0.1s

Not release

C type

1~63

Cold state

10In

T<0.1s

Release

C type

1~63

Cold state

10In

T≥0.1s

Not release

D type

1~63

Cold state

14In

T<0.1s

Release

D type